TIER-Ready III Prefabricated Modular Data Center Solution

A-RACK’s high prefabricated data center EDGEasyfree full series ranging from 50kw-300kw have successfully achieved TIER-Ready III certification of Uptime Institute. The TIER-Ready EDGEasyfree series consists of five basic topological units with the same TIER III topology. Each BTU unit is standardized design and prefabricated production. Through the flexible combination of the basic BTU, customer not only can directly have 50kw to 300kw TIER READY data center, but also can easily achieve the TIER-Ready Data Center over 300KW by real TIER III level prefabricated deployment.

EDGEasy Free:
Quantity:
  • EDGEasyfree
  • A-RACK


Summary:         Features&Benefits                  

Applications:       

A-RACK's EDGEasy Free natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operationand maintenance through intelligent management and operation software. 


  • Save Time & Money

  • Rapid Deployment

  • Stable, Reliable& Scalable

  • Self-Monitoring Real-Time

  • PLC Control

  • Self-Regulating Climate Control


  • Small Data Centers

  • Schools

  • Hospitals

  • Financial Institutions

  • Electronic sports



R4-44-ENG

Specifications


Physical Measurement         

5126 mm(W)x 2250mm(D)x 2950mm(H)

Rack Size            4 pcs 535 mm ( W) x 800 mm ( D ) x 42U(H)   
Weight       2200Kg            
Max. IT Loading     44 kW            
Max. Cooling Capacity              50 kW            

 Power Distribution


Nominal Input Voltage   380 V AC, 3PH, 50 Hz            
Maximum Input Current              100 A            
Power Distribution Panel             Busbar                        
PDU             Rackmount, 25A,AP1000 series, (2) per rack     
Input 380V, output (18) C13+ (6) C19               
UPS             54kW per UPS; on-line dual transform mode (optional)           
Battery                   VRLA –(optional)          
Backup Time  5 min @ full load capacity ( adjustable )  

Cooling


Type               Natural fresh air + Evaporation + Supplemental cooling            
Capacity    
50 kW            
Internal Operation Humidity  
10% - 95%            
Internal Operation Temperature    15.6℃ ~ 26.7℃            

 Monitor & Control System and Security System


DSCV Management System         Power, cooling, security, environment monitoring & control, PUE display                     
Exits             3 main exits and 1 maintenance exit          
Sensors             T/H & smoke sensor x4;electric lock x 4;leak sensor x 2            
HMI     10” tactile screen                
Serial Server     RS485,TCP/IP               
Monitoring points                 
           
Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc.            
Alarm point                 
           
Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm.          
Telecommunication    MODUBUS/TCP(Standard)、MQTT etc.

 Operation Condition


               

Operation Condition                

           

Elevation: 0 -3280ft (max. 9842ft derate )    

Temperature :5 ℉ ~ 113℉/-20℃~45℃   
Humidity :5-100% RH, non-condensing 
Seismic Grade Optional                     

 Option Model


Power Distribution        Smart busbar, power distribution panel        
UPS             54 kW on-line double conversion            
PDU             Switch / meter,  output (18) C13+(6) C19  
Supplemental Cooling 
DX                  
L Bracket            
Installed to 19”rack, loading 110lbs (50kgs)  
Blanking Panel
1U, 2U, 4U toolless mounting            
Door Lock   
Tactile electrical lock                        
Door Access        
Finger print, face recognition system  
T/H & smoke Sensor  T/H & smoke sensor,RS485            
Leak Sensor             RS485            
Lighting 
24V LED light, 11”(300mm)(with on/off, can be serial connected)

Compliant


EMC             EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3            
Qualification   
UL,TUV,EMC, CE, EN/IEC 60950-1            
Environment      
ROHS, WEEE            

 



Summary:           

Features&Benefits               

Applications:       

A-RACK's EDGEasy Free   natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software. 

     
  • Save Time & Money

  • Rapid Deployment

  • Stable, Reliable& Scalable

  • Self-Monitoring Real-Time

  • PLC Control

  • Self-Regulating Climate Control

           

  • Small Data Centers

  • Schools

  • Hospitals

  • Financial Institutions

  • Electronic sports



R10-100-ENG

Specifications


Physical Measurement  

5700 mm(W)x 6000mm(D)x 3450mm(H)
    

Rack Size               10pcs 550 mm ( W) x 1000 mm ( D ) x 42U(H)
Weight               5000Kg            
Max. IT Loading     100 kW            
Max. Cooling Capacity          120 kW            

 Power Distribution


Nominal Input Voltage        380 V AC, 3PH, 50 Hz            
Maximum Input Current               200 A            
Power Distribution Panel       Busbar     
PDU             Rackmount, 16A,AP1000 series, (2) per rack 
Input 380V, output (18) C13+ (6) C19  
UPS             108kW per UPS; on-line dual transform mode (optional)       
Battery    VRLA –(optional)        
Backup Time  
5 min @ full load capacity ( adjustable ) 

Cooling


Type                 
           
Natural fresh air + Evaporation + Supplemental cooling             
Capacity        
120 kW            
Internal  Operation Humidity 
10% - 95%            

Internal Operation

Temperature          

15.6℃ ~ 26.7℃            

 Monitor & Control System and Security System


DSCV Management System          
Power, cooling, security, environment monitoring & control, PUE display    
Exits             4 main exits and 2 maintenance exit   
Sensors             T/H & smoke sensor x 10;electric lock x 6;leak sensor x 5            
HMI                   15” tactile screen          
Serial Server    
RS485,TCP/IP          
Monitoring points            Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc.            
Alarm point         
Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm.       
Telecommunication             
MODUBUS/TCP(Standard)、MQTT etc      

 Operation Condition


               

Operation Condition           

Elevation: 0 -3280ft (max. 9842ft derate )     

Temperature :5 ℉ ~ 113℉/-20℃~45℃             
Humidity :5-100% RH, non-condensing             
Seismic Grade        Optional  

 Option Model


Power Disribution   Smart busbar, power distribution panel    
UPS             108 kW on-line double conversion            
PDU             Switch / meter,  output (18) C13+(6) C19
Supplemental Cooling 
DX                
L Bracket                  Installed to 19”rack, loading 110lbs (50kgs) 
Blanking Panel
1U, 2U, 4U toolless mounting                 
Door Lock  
Tactile electrical lock             
Door Access       Finger print, face recognition system   
T/H & smoke Sensor  T/H & smoke sensor,RS485            
Leak Sensor             RS485            
Lighting                 
           
24V LED light, 11”(300mm)(with on/off, can be serial connected   

Compliant


EMC             EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3            
Qualification  UL,TUV,EMC, CE, EN/IEC 60950-1            
Environment 
ROHS, WEEE            

 



Summary:               Features&Benefits          

Applications:        

A-RACK's EDGEasy Free   natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software. 


  • Save Time & Money

  • Rapid Deployment

  • Stable, Reliable& Scalable

  • Self-Monitoring Real-Time

  • PLC Control

  • Self-Regulating Climate Control

           

  • Small Data Centers

  • Schools

  • Hospitals

  • Financial Institutions

  • Electronic sports


R20M-100-ENG

Specifications


Physical Measurement 

4000 mm(W)x 7500mm(D)x 2300mm(H)
              

Rack Size  20pcs 600 mm ( W) x 900 mm ( D ) x 42U(H) 
Weight     6500Kg            
Max. IT Loading   100 kW            
Max. Cooling Capacity                 120 kW            

 Power Distribution


Nominal Input Voltage                   380 V AC, 3PH, 50 Hz            
Maximum Input Current    200 A            
Power Distribution Panel    
Busbar                 
PDU             Rackmount, 32A,AP1000 series, (2) per rack       
Input 230V, output (20) C13+ (4) C19 
UPS             108kW per UPS; on-line dual transform mode (optional)              
Battery         VRLA –(optional)                         
Backup Time  5 min @ full load capacity ( adjustable )     

Cooling


Type               Natural fresh air + Evaporation + Supplemental cooling          
Capacity          
120 kW            
Internal  Operation Humidity              10% - 95%            
Internal Operation Temperature          15.6℃ ~ 26.7℃            

 Monitor & Control System and Security System


DSCV Management System                  Power, cooling, security, environment monitoring & control, PUE display                     
Exits             1 main exits and 3 maintenance exit                  
Sensors             T/H & smoke sensor x 20; electric lock x 4;leak sensor x 10          
HMI                  15” tactile screen                 
Serial Server            RS485,TCP/IP 
Monitoring points                 
           
Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc.              
Alarm point                 
           
Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm.                 
Telecommunication 
MODUBUS/TCP(Standard)、MQTT etc        

 Operation Condition


Operation Condition    

Elevation: 0 -3280ft (max. 9842ft derate )      

Temperature :5 ℉ ~ 113℉/-20℃~45℃  
Humidity :5-100% RH, non-condensing         
Seismic Grade        Optional                    

 Option Model


Power Distribution          Smart busbar, power distribution panel  
UPS             108 kW on-line double conversion            
PDU             Switch / meter,  output (20) C13+(4) C19  
Supplemental Cooling     DX                      
L Bracket     Installed to 19”rack, loading 110lbs (50kgs)  
Blanking Panel 1U, 2U, 4U toolless mounting            
Door Lock Tactile electrical lock                 
Door Access  Finger print, face recognition system       
T/H & smoke Sensor  T/H & smoke sensor,RS485            
Leak Sensor     RS485            
Lighting         24V LED light, 11”(300mm)(with on/off, can be serial connected)        

Compliant


EMC             EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3            
Qualification UL,TUV,EMC, CE, EN/IEC 60950-1            
Environment          ROHS, WEEE            

 



Summary:            Features&Benefits               

Applications:       

A-RACK's EDGEasy Free   natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software.                
           

  • Save Time & Money

  • Rapid Deployment

  • Stable, Reliable& Scalable

  • Self-Monitoring Real-Time

  • PLC Control

  • Self-Regulating Climate Control

           

  • Small Data Centers

  • Schools

  • Hospitals

  • Financial Institutions

  • Electronic sports



R10-100-ENG

Specifications


Physical Measurement  

5700 mm(W)x 11300mm(D)x 3450mm(H)

Rack Size               20pcs 550 mm ( W) x 1000 mm ( D ) x 42U(H)
Weight               9000Kg            
Max. IT Loading     250 kW            
Max. Cooling Capacity          270 kW            

 Power Distribution


Nominal Input Voltage        380 V AC, 3PH, 50 Hz            
Maximum Input Current               400 A            
Power Distribution Panel       Busbar     
PDU             Rackmount, 25A,AP1000 series, (2) per rack 
Input 380V, output (18) C13+ (6) C19  
UPS             270kW per UPS; on-line dual transform mode (optional)       
Battery    VRLA –(optional)        
Backup Time  
5 min @ full load capacity ( adjustable ) 

Cooling


Type                 
           
Natural fresh air + Evaporation + Supplemental cooling             
Capacity        
270 kW            
Internal  Operation Humidity 
10% - 95%            

Internal Operation

Temperature          

15.6℃ ~ 26.7℃            

 Monitor & Control System and Security System


DSCV Management System          
Power, cooling, security, environment monitoring & control, PUE display    
Exits             7 main exits and 4 maintenance exit   
Sensors             T/H & smoke sensor x 20;electric lock x 11; leak sensor x 10            
HMI                   15” tactile screen          
Serial Server    
RS485,TCP/IP          
Monitoring points            Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc.            
Alarm point         
Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm.       
Telecommunication             
MODUBUS/TCP(Standard)、MQTT etc      

 Operation Condition


               

Operation Condition           

Elevation: 0 -3280ft (max. 9842ft derate )     

Temperature :5 ℉ ~ 113℉/-20℃~45℃             
Humidity :5-100% RH, non-condensing             
Seismic Grade        Optional  

 Option Model


Power Disribution   Smart busbar, power distribution panel    
UPS             270 kW on-line double conversion            
PDU             Switch / meter,  output (18) C13+(6) C19
Supplemental Cooling 
DX                
L Bracket                  Installed to 19”rack, loading 110lbs (50kgs) 
Blanking Panel
1U, 2U, 4U toolless mounting                 
Door Lock  
Tactile electrical lock             
Door Access       Finger print, face recognition system   
T/H & smoke Sensor  T/H & smoke sensor,RS485            
Leak Sensor             RS485            
Lighting                
24V LED light, 11”(300mm)(with on/off, can be serial connected   

Compliant


EMC             EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3            
Qualification  UL,TUV,EMC, CE, EN/IEC 60950-1            
Environment 
ROHS, WEEE            

 



Summary:               Features&Benefits                  

Applications:          

A-RACK's EDGEasy Free   natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software.  
  • Save Time & Money             

  • Rapid Deployment     

  • Stable, Reliable& Scalable     

  • Self-Monitoring Real-Time   

  • PLC Control     

  • Self-Regulating Climate Control                

     

  • Small Data

  • Centers          

  • Schools           

  • Hospitals

  • Financial

  • Institutions   

  • Electronic sports

R30M-300-ENG
Specifications


Physical Measurement 

5800 mm(W)x 3000mm(D)x 5100mm(H)

Weight        

3000Kg            

Max. IT Loading  

300 kW            

Max. Cooling Capacity           

300 kW            

 Power Distribution


Nominal Input Voltage      380 V AC, 3PH, 50 Hz            
Maximum Input Current   600 A            
Power Distribution Panel          Busbar                        
UPS             360kW per UPS; on-line dual transform mode (optional)           
Battery      
VRLA –(optional)             
Backup Time        5 min @ full load capacity ( adjustable )    

Cooling


Type                 
           
Natural fresh air + Evaporation + Supplemental cooling          
Capacity     
300 kW            
Internal Operation Humidity       
10% - 95%            

Internal Operation

Temperature  

15.6℃ ~ 26.7℃              

 Monitor & Control System and Security System


DSCV Management System           
Power, cooling, security, environment monitoring & control, PUE display            
Exits

2 main exits and 2 maintenance exit        

Sensors     electric lock x 4  
HMI   
15” tactile screen         
Serial Server     
RS485,TCP/IP                     
Monitoring points                 
           
Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc.                    
Alarm point    
Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm.   
Telecommunication 
MODUBUS/TCP(Standard)、MQTT etc.

 Operation Condition


Operation Condition  

Elevation: 0 -3280ft (max. 13123ft derate )    

Temperature :5 ℉ ~ 113℉/-20℃~45℃        
Humidity :5-100% RH, non-condensing         
Seismic Grade      Optional      

 Option Model


Power Distribution    Smart busbar, power distribution panel                  
UPS             360 kW on-line double conversion     
Supplemental Cooling            DX                   
L Bracket        
Installed to 19”rack, loading 110lbs (50kgs) 
Blanking Panel     
1U, 2U, 4U toolless mounting         
Door Lock              Tactile electrical lock            
Door Access         
Finger print, face recognition system    
T/H & smoke Sensor T/H & smoke sensor,RS485            
Leak Sensor     RS485            
Lighting     24V LED light, 11”(300mm)(with on/off, can be serial connected)                    

Compliant


EMC             EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3            
Qualification UL,TUV,EMC, CE, EN/IEC 60950-1            
Environment          ROHS, WEEE            

 