A-RACK’s high prefabricated data center EDGEasyfree full series ranging from 50kw-300kw have successfully achieved TIER-Ready III certification of Uptime Institute. The TIER-Ready EDGEasyfree series consists of five basic topological units with the same TIER III topology. Each BTU unit is standardized design and prefabricated production. Through the flexible combination of the basic BTU, customer not only can directly have 50kw to 300kw TIER READY data center, but also can easily achieve the TIER-Ready Data Center over 300KW by real TIER III level prefabricated deployment.
EDGEasy Free: | |
---|---|
Quantity: | |
Summary: | Features&Benefits | Applications: |
A-RACK's EDGEasy Free natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operationand maintenance through intelligent management and operation software. |
|
|
Specifications
Physical Measurement | 5126 mm(W)x 2250mm(D)x 2950mm(H) |
Rack Size | 4 pcs 535 mm ( W) x 800 mm ( D ) x 42U(H) |
Weight | 2200Kg |
Max. IT Loading | 44 kW |
Max. Cooling Capacity | 50 kW |
Power Distribution
Nominal Input Voltage | 380 V AC, 3PH, 50 Hz |
Maximum Input Current | 100 A |
Power Distribution Panel | Busbar |
PDU | Rackmount, 25A,AP1000 series, (2) per rack |
Input 380V, output (18) C13+ (6) C19 | |
UPS | 54kW per UPS; on-line dual transform mode (optional) |
Battery | VRLA –(optional) |
Backup Time | 5 min @ full load capacity ( adjustable ) |
Cooling
Type | Natural fresh air + Evaporation + Supplemental cooling |
Capacity | 50 kW |
Internal Operation Humidity | 10% - 95% |
Internal Operation Temperature | 15.6℃ ~ 26.7℃ |
Monitor & Control System and Security System
DSCV Management System | Power, cooling, security, environment monitoring & control, PUE display |
Exits | 3 main exits and 1 maintenance exit |
Sensors | T/H & smoke sensor x4;electric lock x 4;leak sensor x 2 |
HMI | 10” tactile screen |
Serial Server | RS485,TCP/IP |
Monitoring points | Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc. |
Alarm point | Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm. |
Telecommunication | MODUBUS/TCP(Standard)、MQTT etc. |
Operation Condition
Operation Condition | Elevation: 0 -3280ft (max. 9842ft derate ) |
Temperature :5 ℉ ~ 113℉/-20℃~45℃ | |
Humidity :5-100% RH, non-condensing | |
Seismic Grade | Optional |
Option Model
Power Distribution | Smart busbar, power distribution panel |
UPS | 54 kW on-line double conversion |
PDU | Switch / meter, output (18) C13+(6) C19 |
Supplemental Cooling | DX |
L Bracket | Installed to 19”rack, loading 110lbs (50kgs) |
Blanking Panel | 1U, 2U, 4U toolless mounting |
Door Lock | Tactile electrical lock |
Door Access | Finger print, face recognition system |
T/H & smoke Sensor | T/H & smoke sensor,RS485 |
Leak Sensor | RS485 |
Lighting | 24V LED light, 11”(300mm)(with on/off, can be serial connected) |
Compliant
EMC | EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 |
Qualification | UL,TUV,EMC, CE, EN/IEC 60950-1 |
Environment | ROHS, WEEE |
Summary: | Features&Benefits | Applications: |
A-RACK's EDGEasy Free natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software. |
|
|
Specifications
Physical Measurement | 5700 mm(W)x 6000mm(D)x 3450mm(H) |
Rack Size | 10pcs 550 mm ( W) x 1000 mm ( D ) x 42U(H) |
Weight | 5000Kg |
Max. IT Loading | 100 kW |
Max. Cooling Capacity | 120 kW |
Power Distribution
Nominal Input Voltage | 380 V AC, 3PH, 50 Hz |
Maximum Input Current | 200 A |
Power Distribution Panel | Busbar |
PDU | Rackmount, 16A,AP1000 series, (2) per rack |
Input 380V, output (18) C13+ (6) C19 | |
UPS | 108kW per UPS; on-line dual transform mode (optional) |
Battery | VRLA –(optional) |
Backup Time | 5 min @ full load capacity ( adjustable ) |
Cooling
Type | Natural fresh air + Evaporation + Supplemental cooling |
Capacity | 120 kW |
Internal Operation Humidity | 10% - 95% |
Internal Operation Temperature | 15.6℃ ~ 26.7℃ |
Monitor & Control System and Security System
DSCV Management System | Power, cooling, security, environment monitoring & control, PUE display |
Exits | 4 main exits and 2 maintenance exit |
Sensors | T/H & smoke sensor x 10;electric lock x 6;leak sensor x 5 |
HMI | 15” tactile screen |
Serial Server | RS485,TCP/IP |
Monitoring points | Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc. |
Alarm point | Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm. |
Telecommunication | MODUBUS/TCP(Standard)、MQTT etc |
Operation Condition
Operation Condition | Elevation: 0 -3280ft (max. 9842ft derate ) |
Temperature :5 ℉ ~ 113℉/-20℃~45℃ | |
Humidity :5-100% RH, non-condensing | |
Seismic Grade | Optional |
Option Model
Power Disribution | Smart busbar, power distribution panel |
UPS | 108 kW on-line double conversion |
PDU | Switch / meter, output (18) C13+(6) C19 |
Supplemental Cooling | DX |
L Bracket | Installed to 19”rack, loading 110lbs (50kgs) |
Blanking Panel | 1U, 2U, 4U toolless mounting |
Door Lock | Tactile electrical lock |
Door Access | Finger print, face recognition system |
T/H & smoke Sensor | T/H & smoke sensor,RS485 |
Leak Sensor | RS485 |
Lighting | 24V LED light, 11”(300mm)(with on/off, can be serial connected |
Compliant
EMC | EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 |
Qualification | UL,TUV,EMC, CE, EN/IEC 60950-1 |
Environment | ROHS, WEEE |
Summary: | Features&Benefits | Applications: |
A-RACK's EDGEasy Free natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software. |
|
|
Specifications
Physical Measurement | 4000 mm(W)x 7500mm(D)x 2300mm(H) |
Rack Size | 20pcs 600 mm ( W) x 900 mm ( D ) x 42U(H) |
Weight | 6500Kg |
Max. IT Loading | 100 kW |
Max. Cooling Capacity | 120 kW |
Power Distribution
Nominal Input Voltage | 380 V AC, 3PH, 50 Hz |
Maximum Input Current | 200 A |
Power Distribution Panel | Busbar |
PDU | Rackmount, 32A,AP1000 series, (2) per rack |
Input 230V, output (20) C13+ (4) C19 | |
UPS | 108kW per UPS; on-line dual transform mode (optional) |
Battery | VRLA –(optional) |
Backup Time | 5 min @ full load capacity ( adjustable ) |
Cooling
Type | Natural fresh air + Evaporation + Supplemental cooling |
Capacity | 120 kW |
Internal Operation Humidity | 10% - 95% |
Internal Operation Temperature | 15.6℃ ~ 26.7℃ |
Monitor & Control System and Security System
DSCV Management System | Power, cooling, security, environment monitoring & control, PUE display |
Exits | 1 main exits and 3 maintenance exit |
Sensors | T/H & smoke sensor x 20; electric lock x 4;leak sensor x 10 |
HMI | 15” tactile screen |
Serial Server | RS485,TCP/IP |
Monitoring points | Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc. |
Alarm point | Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm. |
Telecommunication | MODUBUS/TCP(Standard)、MQTT etc |
Operation Condition
Operation Condition | Elevation: 0 -3280ft (max. 9842ft derate ) |
Temperature :5 ℉ ~ 113℉/-20℃~45℃ | |
Humidity :5-100% RH, non-condensing | |
Seismic Grade | Optional |
Option Model
Power Distribution | Smart busbar, power distribution panel |
UPS | 108 kW on-line double conversion |
PDU | Switch / meter, output (20) C13+(4) C19 |
Supplemental Cooling | DX |
L Bracket | Installed to 19”rack, loading 110lbs (50kgs) |
Blanking Panel | 1U, 2U, 4U toolless mounting |
Door Lock | Tactile electrical lock |
Door Access | Finger print, face recognition system |
T/H & smoke Sensor | T/H & smoke sensor,RS485 |
Leak Sensor | RS485 |
Lighting | 24V LED light, 11”(300mm)(with on/off, can be serial connected) |
Compliant
EMC | EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 |
Qualification | UL,TUV,EMC, CE, EN/IEC 60950-1 |
Environment | ROHS, WEEE |
Summary: | Features&Benefits | Applications: |
A-RACK's EDGEasy Free natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software. |
|
|
Specifications
Physical Measurement | 5700 mm(W)x 11300mm(D)x 3450mm(H) |
Rack Size | 20pcs 550 mm ( W) x 1000 mm ( D ) x 42U(H) |
Weight | 9000Kg |
Max. IT Loading | 250 kW |
Max. Cooling Capacity | 270 kW |
Power Distribution
Nominal Input Voltage | 380 V AC, 3PH, 50 Hz |
Maximum Input Current | 400 A |
Power Distribution Panel | Busbar |
PDU | Rackmount, 25A,AP1000 series, (2) per rack |
Input 380V, output (18) C13+ (6) C19 | |
UPS | 270kW per UPS; on-line dual transform mode (optional) |
Battery | VRLA –(optional) |
Backup Time | 5 min @ full load capacity ( adjustable ) |
Cooling
Type | Natural fresh air + Evaporation + Supplemental cooling |
Capacity | 270 kW |
Internal Operation Humidity | 10% - 95% |
Internal Operation Temperature | 15.6℃ ~ 26.7℃ |
Monitor & Control System and Security System
DSCV Management System | Power, cooling, security, environment monitoring & control, PUE display |
Exits | 7 main exits and 4 maintenance exit |
Sensors | T/H & smoke sensor x 20;electric lock x 11; leak sensor x 10 |
HMI | 15” tactile screen |
Serial Server | RS485,TCP/IP |
Monitoring points | Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc. |
Alarm point | Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm. |
Telecommunication | MODUBUS/TCP(Standard)、MQTT etc |
Operation Condition
Operation Condition | Elevation: 0 -3280ft (max. 9842ft derate ) |
Temperature :5 ℉ ~ 113℉/-20℃~45℃ | |
Humidity :5-100% RH, non-condensing | |
Seismic Grade | Optional |
Option Model
Power Disribution | Smart busbar, power distribution panel |
UPS | 270 kW on-line double conversion |
PDU | Switch / meter, output (18) C13+(6) C19 |
Supplemental Cooling | DX |
L Bracket | Installed to 19”rack, loading 110lbs (50kgs) |
Blanking Panel | 1U, 2U, 4U toolless mounting |
Door Lock | Tactile electrical lock |
Door Access | Finger print, face recognition system |
T/H & smoke Sensor | T/H & smoke sensor,RS485 |
Leak Sensor | RS485 |
Lighting | 24V LED light, 11”(300mm)(with on/off, can be serial connected |
Compliant
EMC | EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 |
Qualification | UL,TUV,EMC, CE, EN/IEC 60950-1 |
Environment | ROHS, WEEE |
Summary: | Features&Benefits | Applications: |
A-RACK's EDGEasy Free natural cooling module is a prefabricated and efficient data center solution. A-RACK natural cooling solution integrates multiple physical infrastructure subsystems; all components are fully prefabricated and tested in the factory before it is delivered to the customer site. A-RACK natural cooling module helps customers realize rapid deployment, end-to-end one-stop delivery and digital operation and maintenance through intelligent management and operation software. |
|
|
Specifications
Physical Measurement | 5800 mm(W)x 3000mm(D)x 5100mm(H) |
Weight | 3000Kg |
Max. IT Loading | 300 kW |
Max. Cooling Capacity | 300 kW |
Power Distribution
Nominal Input Voltage | 380 V AC, 3PH, 50 Hz |
Maximum Input Current | 600 A |
Power Distribution Panel | Busbar |
UPS | 360kW per UPS; on-line dual transform mode (optional) |
Battery | VRLA –(optional) |
Backup Time | 5 min @ full load capacity ( adjustable ) |
Cooling
Type | Natural fresh air + Evaporation + Supplemental cooling |
Capacity | 300 kW |
Internal Operation Humidity | 10% - 95% |
Internal Operation Temperature | 15.6℃ ~ 26.7℃ |
Monitor & Control System and Security System
DSCV Management System | Power, cooling, security, environment monitoring & control, PUE display |
Exits | 2 main exits and 2 maintenance exit |
Sensors | electric lock x 4 |
HMI | 15” tactile screen |
Serial Server | RS485,TCP/IP |
Monitoring points | Input voltage , current, frequency, active power, harmonic measurement, on/off , cooling temperature, cooling operation status, temperature, humidity, smoke, leak, door access etc. |
Alarm point | Power failure alarm, over-voltage alarm, currency over loading alarm, on/off switching alarm, over heat alarm, leak alarm, smoke alarm. |
Telecommunication | MODUBUS/TCP(Standard)、MQTT etc. |
Operation Condition
Operation Condition | Elevation: 0 -3280ft (max. 13123ft derate ) |
Temperature :5 ℉ ~ 113℉/-20℃~45℃ | |
Humidity :5-100% RH, non-condensing | |
Seismic Grade | Optional |
Option Model
Power Distribution | Smart busbar, power distribution panel |
UPS | 360 kW on-line double conversion |
Supplemental Cooling | DX |
L Bracket | Installed to 19”rack, loading 110lbs (50kgs) |
Blanking Panel | 1U, 2U, 4U toolless mounting |
Door Lock | Tactile electrical lock |
Door Access | Finger print, face recognition system |
T/H & smoke Sensor | T/H & smoke sensor,RS485 |
Leak Sensor | RS485 |
Lighting | 24V LED light, 11”(300mm)(with on/off, can be serial connected) |
Compliant
EMC | EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 |
Qualification | UL,TUV,EMC, CE, EN/IEC 60950-1 |
Environment | ROHS, WEEE |